MDS MDS iNET 900 Instrukcja Użytkownika Strona 15

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 22
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 14
MDS 05-4131A01, Rev. A MDS iNET ENI Supplement 15
3. MODBUS to MODBUS
TCP SERVER PROTOCOL
3.1 Introduction
NOTE: This section assumes you have an understanding of Ethernet
networking, TCP/IP, and Modbus serial protocols. For more
information, refer to the Modbus-IDA Organization web site:
http://www.modbus.org.
The iNET implementation of the MODBUS to MODBUS TCP server
protocol is limited to act as one of the following:
A Modbus/TCP client on the LAN port
A Modbus ASCII server on the serial port
A Modbus RTU server (user configurable) on the serial port
NOTE: Modbus/TCP functionality is only available on the COM2 port
of the iNET/ENI transceiver.
NOTE: All requests are sent using TCP on registered port 502.
NOTE: The PLC’s User ID must match the last octet of the iNET
Remote’s IP address. See Figure 3-1.
Figure 3-1 PLC User ID Example
PLC
User ID: 23
i
NET Remote
I
P Address: 192.158.16.23